Produit Centre |
|
| Electric Measure & Controll > Analyseur Harmonique |
|
| Analyseur Harmonique |
| 1.General |

|
PZ96 Series programmable haromanic analyzers can measure all the data of all kinds of electrical network. And they have the function of multi rate in multi zone of energy count. At the same time, they can measure more than 31 ranges of haromanic and display waveform or bargraph. They comply EN 61326:2006 and EN 61010-1:2001.
They are equipped with RS-485 port (Modbus-RTU protocol), and they can be chosen by 2 logic outputs and 4 logic inputs.
With the 4 or 5 keys on the front, we can change the read data and the parameter of range, ratio, communication etc.. |
| 2.Technical feature |
 |
| |
Technical parameters |
Values |
| INPUT |
Measurable |
all the parameters of electrical networks
more than 30 ranges of haromanic |
| Network |
Single-phase network; 3-phase balanced network
3-phase unbalanced, 3 wires; 3-phase unbalanced, 4 wires |
| Frequence |
45~65Hz |
| Voltage |
AC 100V,400V |
| Overload: 480V (continuous); 800V during 1s |
| Power draw: < 0.2VA |
| Current |
AC 1A, 5A |
| Overload: 6A (continuous); 50A during 1s |
| Power draw: < 0.2VA |
| CT / PT ratio |
1~9999 programmable |
| OTHER FEATURES |
Precision |
kWh 0.5%, kvarh 1% |
| Supply |
AC/DC 85~270V, Consumption≤4VA |
| Test voltage |
2kVAC (voltage input / supply) |
| 2.5kVAC (current input / supply) |
| Isulation resistence:input/housing; output/housing >100MΩ |
| ENV |
Temperature |
Work:-10℃~55℃ |
| |
Storage:-20℃~+70℃ |
| Humidity |
5%~95% |
| Altitude |
≤2500m |
|
| |
| 3. Options |
| OPTIONS |
FEATURES |
| Communication (/C) |
RS485, Modbus-RTU protocol; 1 start bit, 8 data bit, 1 stop bit,
no parity, 1200/2400/4800/9600/19200 bps etc |
| Logic (/K) |
4 logic inputs and 2 logic outputs |
| Logic Input: dry contact Input, supplied inside, optoisolator |
Relay output: NO-NC contact; capacity: 1A/30VDC,5A/250VAC
(for control other equipment remotely) |
| Energy pulse output |
Output mode: 2 channels open-collector photocoupler pulse |
| Pulse constant: 10k,40k, 160k imp/kWh |
| Multi tarrif (/F) |
4 tarrifs and 8 zones in 24 hours |
|
| |
| 4.Specification |
| Model |
Outline |
Types |
Description |
 |
96 X 96 mm |
PZ96L-EH |
All the parameters of electrical network, and THDu THDi, 2-31 ranges haromanic |
 |
96 X 96 mm |
PZ96L-3EH |
- MEASURE: 3 phase voltage, 3 line voltage, 3 current, 4P, 4Q, 4S, 4 cos;
- HARMONIC: the data of current and voltage harmonic (2-31 ranges), harmonic bar graph and harmonic wave;
- NETWORK: crest factor, THFF, KF, UF, voltage peak, voltage vector, current vector;
- kWh: this month, last month, before last month multi tariff kWh and total kWh;
- SWITCHING: Memory the states of switches of input and output;
- SOE: (Sequence Of Event) |
 |
120 X 120 mm |
PZ42L-EH |
All the parameters of electrical network, and THDu THDi, 2-31 ranges haromanic |
|
|